552 Fieldbus control through the embedded fieldbus interface (EFB)

Actual values

The ABB Drives profile supports the use of two fieldbus actual values, ACT1 and
ACT2. The actual values are 16-bit words each containing a sign bit and a 15-bit
integer. A negative value is formed by calculating the two's complement from the
corresponding positive value.
The actual values are scaled as defined by parameters 46.01...46.04; which scaling
is in use depends on the setting of parameters
act2 type
(see page 356).
Fieldbus
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
46.01
(with speed reference)
20000
46.02
(with frequency reference)
46.03
(with torque reference)
10000
46.04
(with power reference)
0
0
-(46.03) (with torque reference)
-10000
-(46.04) (with power reference)
-(46.01) (with speed reference)
-20000
-(46.02) (with frequency reference)
58.28 EFB act1 type