ABB ACS880 Firmware Manual page 279

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

No.
Name/Value
Both
Abs both
32.06
Supervision 1
action
No action
Warning
Fault
Fault if running
32.07
Supervision 1
signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Process PID output
Process PID
feedback
Other
32.08
Supervision 1 filter
time
0.000 ... 30.000 s
32.09
Supervision 1 low
-21474830.00 ...
21474830.00
32.10
Supervision 1 high
-21474830.00 ...
21474830.00
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Selects the action the drive takes when the value monitored
by signal supervision 1 exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No action taken.
A warning
(A8B0 Signal
supervision) is generated.
The drive trips on
80B0 Signal
If running, the drive trips on
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
(page 115).
01.06 Output frequency
(page 115).
01.07 Motor current
(page 115).
01.10 Motor torque
(page 115).
01.11 DC voltage
(page 115).
01.14 Output power
(page 116).
12.11 AI1 actual value
(page 158).
12.21 AI2 actual value
(page 160).
23.01 Speed ref ramp input
23.02 Speed ref ramp output
24.01 Used speed reference
26.02 Torque reference used
28.02 Frequency ref ramp output
40.01 Process PID output actual
40.02 Process PID feedback actual
Source selection (see
Terms and abbreviations
Defines a filter time constant for the signal monitored by signal
supervision 1.
Signal filter time.
Defines the lower limit for signal supervision 1.
Low limit.
Defines the upper limit for signal supervision 1.
Upper limit.
supervision.
80B0 Signal
supervision.
(page 218).
(page 218).
(page 224).
(page 240).
(page 246).
(page 306).
(page 306).
on page 112). -
Parameters 279
Def/FbEq16
5
6
No action
0
1
2
3
Zero
0
1
3
4
6
7
8
9
10
18
19
20
21
22
24
25
0.000 s
1000 = 1 s
0.00
-
0.00
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents