ABB ACS880 Firmware Manual page 513

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Fault
(hex)
2330
Earth leakage
Programmable fault:
Earth fault
2340
Short circuit
2381
IGBT overload
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
Drive has detected load
unbalance typically due to
31.20
earth fault in motor or motor
cable.
Short-circuit in motor cable(s)
or motor
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and can
be activated by a short circuit
in the motor cable.
Fault tracing 513
What to do
If the control unit is externally powered,
check the setting of parameter
Control board
supply.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check for an earth fault in motor or motor
cables by measuring the insulation
resistances of motor and motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
Motor control
mode.)
With parallel-connected modules, check
the auxiliary code (format XXXY YYZZ).
"Y YY" specifies through which BCU
control unit channel the fault was
received.
If no earth fault can be detected, contact
your local ABB representative.
Check motor and motor cable for cabling
errors.
If the control unit is externally powered,
check the setting of parameter
Control board
supply.
Check that parameter
99.10 Motor
nominal power
has been set correctly.
Check there are no power factor
correction capacitors or surge absorbers
in motor cable.
Check the auxiliary code (format XXXY
YYZZ). With parallel-connected inverter
modules, "Y YY" specifies through which
BCU control unit channel the fault was
received. "ZZ" indicates the location of
the short circuit (0: No detailed
information available, 1: Upper branch of
U-phase, 2: Lower branch of U-phase, 4:
Upper branch of V-phase, 8: Lower
branch of V-phase, 10: Upper branch of
W-phase, 20: Lower branch of W-phase,
other: combinations of the above).
After correcting the cause of the fault,
reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power.
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
95.04
99.04
95.04