200 Parameters
No.
Name/Value
20.19
Enable start
command
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
DIO1
DIO2
DIIL
Other [bit]
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Selects the source for the start enable signal.
1 = Start enable.
With the signal switched off, any drive start command is
inhibited. (Switching the signal off while the drive is running
will not stop the drive.)
Notes:
• If a level-triggered start command is on when the start
enable signal switches on, the drive will start. (An edge-
triggered start signal must be cycled for the drive to start.)
See parameters
20.02 Ext1 start trigger
start trigger type
and
20.29 Local start trigger
• The warning that indicates a missing signal can be
suppressed using parameter
function.
See also parameter
20.12 Run enable 1
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Digital input/output DIO1
(11.02 DIO delayed
Digital input/output DIO2
(11.02 DIO delayed
DIIL input
(10.02 DI delayed
Source selection (see
Terms and abbreviations
type,
20.07 Ext2
type.
20.30 Enable signals warning
source.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
status, bit 0).
status, bit 1).
status, bit 15).
on page 112). -
Def/FbEq16
Selected
0
1
2
3
4
5
6
7
10
11
30