ABB ACS880 Firmware Manual page 296

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

296 Parameters
No.
Name/Value
35.54
Motor nominal
temperature rise
Motor nominal
temperature rise
0...300 °C or
32...572 °F
35.55
Motor thermal time
constant
100 ... 10000 s
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
Defines the temperature rise of the motor above ambient
when the motor is loaded with nominal current. See the motor
manufacturer's recommendations.
The unit is selected by parameter
Temperature
Ambient temperature
Temperature rise.
Defines the thermal time constant for use with the motor
thermal protection model, defined as the time to reach 63% of
the nominal motor temperature. See the motor manufacturer's
recommendations.
Motor current
100%
Temperature rise
100%
63%
Motor thermal time
Motor thermal time constant.
96.16 Unit
selection.
Time
Time
Time
Def/FbEq16
80 °C or
176 °F
1 = 1°
256 s
1 = 1 s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents