No.
Name/Value
96.102 User lock
functionality
Bit
Name
0
Disable ABB access
levels
1
Freeze parameter
lock state
2
Disable file
download
3
Disable FB write to
hidden
4...5
Reserved
6
Protect AP
7
Disable panel
Bluetooth
8...10
Reserved
11
Disable OEM access
level 1
12
Disable OEM access
level 2
13
Disable OEM access
level 3
14...15 Reserved
0000h...FFFFh
96.108 LSU control board
boot
0...1
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Description
(Visible when user lock is open)
Selects the actions or functionalities to be prevented by the
user lock. Note that the changes made take effect only when
the user lock is closed. See parameter
Note: We recommend you select all the actions and
functionalities unless otherwise required by the application.
Information
1 = ABB access levels (service, advanced programmer, etc.; see
96.03) disabled
1 = Changing the parameter lock state prevented, ie. pass code
358 has no effect
1 = Loading of files to drive prevented. This applies to
• firmware upgrades
• safety functions module (FSO-xx) configuration
• parameter restore
• loading an adaptive program
• loading and debugging an application program
• changing home view of control panel
• editing drive texts
• editing the favorite parameters list on control panel
• configuration settings made through control panel such as
time/date formats and enabling/disabling clock display.
1 = Access to parameters on disabled access levels from fieldbus
prevented.
1 = Creating a backup and restoring from a backup prevented.
1 = Bluetooth disabled on ACS-AP-W control panel. If the drive is
part of a panel bus, Bluetooth is disabled on all panels.
1 = OEM access level 1 disabled
1 = OEM access level 2 disabled
1 = OEM access level 3 disabled
Selection of actions to be prevented by user lock.
(Only visible when IGBT supply unit control activated by
95.20)
Changing the value of this parameter to 1 reboots the supply
control unit (without requiring a power off/on cycle of the drive
system).
The value reverts to 0 automatically.
1 = Reboot the supply control unit.
Parameters 423
Def/FbEq16
1000b
96.02 Pass
code.
-
0
1 = 1