ABB ACS880 Firmware Manual page 499

Primary control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

Code
Warning
(hex)
A5EC PU communication
internal
A5ED Measurement circuit
ADC
A5EE
Measurement circuit
DFF
A5EF
PU state feedback
A5F0
Charging feedback
A5F3
Switching frequency
below requested
A5F4
Control unit battery
A682
Flash erase speed
exceeded
A683
Data saving to power
unit
A684
SD card
A686
Checksum mismatch
Programmable warning:
96.54 Checksum action
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Cause
Communication errors
detected between the drive
control unit and the power unit.
Problem with measurement
circuit of power unit (analog to
digital converter)
Problem with current or voltage
measurement of power unit
State feedback from output
phases does not match control
signals.
Charging in progress
Adequate motor control at
requested output frequency
cannot be reached because of
limited switching frequency
(eg. by parameter 95.15).
The battery of the control unit
is low.
The flash memory (in the
memory unit) has been erased
too frequently, compromising
the lifetime of the memory.
An error in saving data to the
power unit.
0 An error is preventing saving
from initializing.
1
2 Write error.
Error related to SD card used
to store data (BCU control unit
only).
1 No SD card
2 SD card write-protected
3 SD card unreadable
The calculated parameter
checksum does not match any
enabled reference checksum.
Fault tracing 499
What to do
Check the connections between the drive
control unit and the power unit.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Informative warning. Wait until charging
finishes before starting the inverter unit.
Informative warning.
Replace control unit battery.
This warning can be suppressed using
parameter 31.40.
Avoid forcing unnecessary parameter
saves by parameter
96.07
parameter writes (such as user logger
triggering through parameters).
Check the auxiliary code (format XYYY
YZZZ). "X" specifies the source of
warning (1: generic flash erase
supervision). "ZZZ" specifies the flash
subsector number that generated the
warning.
Check the auxiliary code. See actions for
each code below.
Cycle the power to the drive. If the
control unit is externally powered, also
reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
its power. If the problem persists, contact
your local ABB representative.
Check the auxiliary code. See actions for
each code below.
Insert a compatible, writable SD card into
the SD CARD slot of the BCU control
unit.
Check that all necessary approved
(reference) checksums (96.56...96.59)
are enabled in
96.55 Checksum control
word.
Check the parameter configuration.
Using
96.55 Checksum control
enable a checksum parameter and copy
the actual checksum into that parameter.
or cyclic
word,

Hide quick links: