568 Fieldbus control through a fieldbus adapter

Contents of the fieldbus Status word (ABB Drives profile)

The upper case boldface text refers to the states shown in the state diagram (page
569).
Bit
Name
0
Ready to switch
ON
1
Ready run
2
Ready ref
3
Tripped
4
Off 2 inactive
5
Off 3 inactive
6
Switch-on inhibited 1
7
Warning
8
At setpoint
9
Remote
10
Above limit
11
User bit 0
12
User bit 1
13
User bit 2
14
User bit 3
15
Reserved
ghv Vertriebs-GmbH | Am Schammacher Feld 47 | 85567 Grafing | Telefon + 49 80 92 81 89 0 | info@ghv.de | www.ghv.de
Value STATE/Description
1
READY TO SWITCH ON.
0
NOT READY TO SWITCH ON.
1
READY TO OPERATE.
0
OFF1 ACTIVE.
1
OPERATION ENABLED.
0
OPERATION INHIBITED. See parameters
word
and
06.25 Drive inhibit status word 2
1
FAULT.
0
No fault.
1
OFF2 inactive.
0
OFF2 ACTIVE.
1
OFF3 inactive.
0
OFF3 ACTIVE.
SWITCH-ON INHIBITED.
0
1
Warning active.
0
No warning active.
1
OPERATING. Actual value equals reference = is within tolerance
limits (see parameters 46.21...46.23).
0
Actual value differs from reference = is outside tolerance limits.
1
Drive control location: REMOTE (EXT1 or EXT2).
0
Drive control location: LOCAL.
-
See parameter
06.29 MSW bit 10
-
See parameter
06.30 MSW bit 11
-
See parameter
06.31 MSW bit 12
-
See parameter
06.32 MSW bit 13
-
See parameter
06.33 MSW bit 14
06.18 Start inhibit status
for the inhibiting condition.