Digital Clipping Function - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Digital clipping function

This function fixes the range of the digital operation value with the maximum digital output value and the minimum digital
output value when the corresponding current or voltage exceeds the input range.
List of output ranges
The following table lists the output ranges of the digital operation values when the digital clipping function is enabled with each
range.
Input range
4 to 20 mA
0 to 20 mA
-20 to +20 mA
1 to 5 V
0 to 5 V
0 to 10 V
-10 to +10 V
User range setting
Setting procedure
Set "Digital clipping enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]
[Application setting]  [Digital clipping function]
Output range of digital operation values
Digital clipping function is enabled
0 to 32000
-32000 to +32000
0 to 32000
-32000 to +32000
Digital clipping function is disabled
-768 to +32767
-32768 to +32767
-768 to +32767
-32768 to +32767
1 FX5-4AD
1.4 Functions
1
39