Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 66

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Stopping the Logging Operation
Logging operation stops (holds) when the preset trigger condition is satisfied and the set points of the data are collected.
A trigger that is generated when the condition is satisfied is called a hold trigger.
To generate a hold trigger, the following two methods are available.
Page 67 Logging hold request
Page 68 Level trigger
When a hold trigger is detected during data collection, the logging operation stops after the points of the data set in 'CH1 Post-
trigger logging points' (Un\G539) are collected.
'CH1 Logging enable/disable setting'
(Un\G535)
'Operating condition setting request'
(Un\G70, b9)
'Operating condition setting completed
flag' (Un\G69, b9)
Hold trigger
Logging hold flag
■Post-trigger logging points
Set the number of data collected in the period from the detection of a hold trigger to logging operation stop to 'CH1 Post-
trigger logging points' (Un\G539).
■Checking that the logging has stopped
Check that 'CH1 Logging hold flag' (Un\G409) is ON (1).
■Checking data when a hold trigger has occurred
The storage location of the data when a hold trigger has occurred can be checked with 'CH1 Trigger pointer' (Un\G437). The
offset value counted from the start address of CH1 Logging data (Un\G10000 to Un\G19999) is stored in 'CH1 Trigger pointer'
(Un\G437).
Ex.
The value stored in Trigger pointer when the logging operation stops under the following conditions
• 'CH1 Post-trigger logging points' (Un\G539): 6505 points
• The data location where a hold trigger has occurred: At the 3500th point.
CH1 Latest pointer = 4
CH1 Head pointer = 5
1 FX5-4AD
64
1.4 Functions
Enable (0)
ON
OFF
ON
OFF
OFF
Address 0
Address 1
Address 2
Address 3
Address 4
Address 5
Address 3499
Address 3500
Address 3501
Address 9998
Address 9999
'CH1 Logging points after trigger'
The data corresponding to the points set in
'CH1 Post-trigger logging points' (Un\G539) is collected.
ON
Latest
Oldest
CH1 Trigger pointer = 3500