Setting example
Ex.
When the output range is set to 0 to 5 V and the input value shift amount is set to +50
Analog output voltage (V)
5
Unadjusted
value
Adjusted
0
value
-50
0
Digital value
Unadjusted value
-50
31950
Precautions
• The warning output, scaling, and rate control functions are executed based on the digital value for which shift-and-add was
performed.
• When the value obtained by adding 'CH1 Input value shift' (Un\G480) to 'CH1 Digital value' (Un\G460) is out of the digital
setting range, a digital value setting range error (error code: 191H) occurs and the check code is stored in 'CH1 Set value
check code' (Un\G400).
• The shift function is enabled only for normal output. If 'CH1 Input value shift' (Un\G480) is set to a value other than 0 while
the wave output function is in use, a Wave output mode Input value shift amount setting error (alarm code: 0B2H) occurs
and 'Warning output signal' (Un\G69, b14) turns on. The wave output continues, but 'CH1 Input value shift' (Un\G480) is not
added to the output wave data.
• After a Wave output mode Input value shift amount setting error occurs, 'Warning output signal' (Un\G69, b14) will not be
turned off even if 0 is set in 'CH1 Input value shift' (Un\G480). To turn off 'Warning output signal' (Un\G69, b14), turn
offonoff 'Warning output clear request' (Un\G70, b14). This turns off 'Warning output signal' (Un\G69, b14), turns off the
ALM LED, and clears the 'Latest alarm code' (Un\G2).
2 FX5-4DA
192
2.4 Functions
Input value
shift amount
Digital value
31950
32000
Adjusted value
0
32000
Analog output voltage (V)
0
5