■When the external power supply turns off during wave output
When the external power supply turns onoff during without, the wave output status of every channel stops and the wave
output fully stops. If the external power supply turns offon at this time, the wave output will not restart.
To restart the wave output, after the external power supply turns offon, check that the status of the analog output module
and the externally connected devices. Then, set 'CH1 Wave output start/stop request' (Un\G462) to Wave output start request
(1).
While the external power supply is off, no Wave output start/stop request is accepted.
CPU module status
CH1 D/A conversion
enable/disable setting (Un\G500)
CH1 Output enable/disable flag
(Un\G70, b1)
CH1 Wave output start/stop
request (Un\G462)
CH1 Wave output status monitor
(Un\G401)
External power supply
Wave data
Output value as per the setting of CH1 Output
setting during wave output stop (Un\G524)
Since the external power supply turned onoff and the wave output stopped, change the CH1 Wave output start/stop request (Un\G462) to Wave output
stop request (0).
To restart the wave output again, change the 'CH1 Wave output start/stop request' (Un\G462) to Wave output stop request (0) before changing it to Wave
output start request (1).
D/A conversion enable (0)
OFF
Wave output
Wave output stop request (0)
start request (1)
Wave output
Wave output stopped (0)
in progress
(1)
ON
Analog output
0 V/0 mA
0 V/0 mA is output.
RUN
ON
Wave output stop request (0)
Wave output start request (1)
Wave output stopped (0)
ON
OFF
Wave output is
not restarted.
Wave output in progress (1)
2 FX5-4DA