Accuracy at thermocouple connection
The accuracy () is given by the following formula:
Full scale Thermocouple accuracy + Cold junction compensation accuracy
Ex.
Accuracy when B thermocouple is used, the operating ambient temperature is 25, and measured temperature is 1000
(1700 - 600) (0.0013) + (1) = 2.5
■Usable thermocouples and conversion accuracy
Usable thermocouples and conversion accuracy are shown as follows.
Usable thermocouple
K
J
T
B
R
S
To stabilize the accuracy, warm-up (supply power) the system for 30 minutes or more after power-on.
Accuracy at resistance temperature detector connection
The accuracy () is given by the following formula:
Conversion accuracy + Temperature characteristic Operating ambient temperature change + Allowable tolerance of used
resistance temperature detector
■Usable resistance temperature detector, accuracy
Usable resistance
temperature detector
Pt100
Ni100
3 FX5-8AD
334
3.2 Specifications
Conversion accuracy
(at operating ambient temperature 255)
1.5
1.2
1.5
2.3
2.5
2.5
Temperature measuring
Accuracy (accuracy for the maximum value of the selected range)
range
at operating ambient temperature
255
0.8
-200 to +850
0.4
-60 to +250
Conversion accuracy
(at operating ambient temperature -20 to +55)
7.3
4.95
6.5
9.8
12.5
12.5
at operating ambient temperature -20
to +55
2.4
1.2