Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 229

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

2.
Set 'CH1 Wave output step action movement amount' (Un\G482) to 8 (8 in forward direction).
(3) Set the CH1 Wave output
step execution movement
amount (Un\G482) to 8 (8 in
forward direction).
Current address
3.
Rewrite the digital input value of address 34992 to 16000, and set 'CH1 Wave output step action movement amount'
(Un\G482) to -6 (6 in reverse direction).
memory areas
(5) Rewrite the digital input
value of address 34992
Current address
(6) Set the CH1 Wave output
step execution movement
amount (Un\G482) to -6 (6
in reverse direction).
Buffer
Digital Input
memory areas
value
Un\G25000
0
Un\G25001
1000
Un\G25002
2000
Un\G25003
3000
Un\G34988
12000
Un\G34989
14000
Un\G34990
16000
Un\G34991
18000
Un\G34992
20000
Un\G34993
22000
Un\G34994
24000
Un\G34995
26000
Un\G34996
28000
30000
Un\G34997
Un\G34998
32000
Buffer
Digital Input
value
Un\G25000
0
Un\G25001
1000
Un\G25002
2000
Un\G25003
3000
12000
Un\G34988
14000
Un\G34989
16000
Un\G34990
18000
Un\G34991
20000
Un\G34992
22000
Un\G34993
24000
Un\G34994
26000
Un\G34995
28000
Un\G34996
30000
Un\G34997
Un\G34998
32000
Analog output
(Digital input value)
10 V
(32000)
5 V
(16000)
0 V
(0)
(4) The analog output module accepts the movement amount.
The address to be output is moved by the movement amount.
Analog output
(Digital input value)
10 V
(32000)
5 V
(16000)
0 V
(0)
16000
(7) The analog output module accepts the movement amount.
The address to be output is moved by the movement amount.
Analog output value
(4) Digital input value (32000)
of Un\G34998 is output in
analog.
(3)
Analog output value
(7) Digital input value (16000)
of Un\G34992 is output in
analog.
(5)
(6)
2 FX5-4DA
2.4 Functions
2
227

Advertisement

Table of Contents
loading

Table of Contents