Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 379

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

• Checking the trigger generation time
The trigger generation time can be checked with 'CH1 Trigger generation time' (Un\G444 to Un\G448).
Ex.
When 'CH1 Trigger generation time' (Un\G444 to Un\G448) is monitored
'CH1 Trigger generation time (First/Last two digits of the year)' (Un\G444)
'CH1 Trigger generation time (Month/Day)' (Un\G445)
'CH1 Trigger generation time (Hour/Minute)' (Un\G446)
'CH1 Trigger generation time (Second/Day of the week)' (Un\G447)
'CH1 Trigger generation time (Millisecond)' (Un\G448)
Item
First two digits of the year/Last two digits of the
year
Month/Day
Hour/Minute
Second
Day of the week
Millisecond (higher-order digits)/Millisecond
(lower-order digits)
*1 These values assume that a trigger is generated at 10:35 and 40.628 seconds on Monday, January 30th, 2017.
b15
First two digits of the year
Millisecond (higher-order digits)
Storage contents
Stored in BCD code.
One of the following values is stored in BCD code.
• Sunday: 00H
• Monday: 01H
• Tuesday: 02H
• Wednesday: 03H
• Thursday: 04H
• Friday: 05H
• Saturday: 06H
Stored in BCD code.
to
b8 b7
Last two digits of the year
Month
Hour
Second
Millisecond (lower-order digits)
to
b0
Day
Minute
Day of the week
*1
Storage example
2017H
0130H
1035H
40H
01H
0628H
3 FX5-8AD
377
3.4 Functions
3