Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 71

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

• Set a value where a hold trigger is generated to 'CH1 Trigger setting value' (Un\G542).
Item
CH1 Trigger setting value (Un\G542)
The following figure shows the relation between setting items to be configured for the initial setting of a level
trigger.
CH Trigger data
CH Digital
operation value
CH Digital output value
Level data 
For example, to generate a hold trigger when a value in CH1 Digital output value exceeds 10000, set it as
follows.
• 'CH1 Level trigger condition setting' (Un\G540): Rise (1)
• 'CH1 Trigger data' (Un\G541): 400
• 'CH1 Trigger setting value' (Un\G542): 10000
CH Hold trigger
condition setting
The condition is established.
>
(Rise (1))
<
(Fall (2))
> or <
(Rise and fall (3))
Set a buffer memory address to be monitored.
Setting range
-32768 to +32767
Set the
condition.
CH Trigger setting value
Set a reference value to generate a trigger.
-32768 to +32767
1
A trigger occurs
1 FX5-4AD
69
1.4 Functions