Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 317

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Alarm output setting
Set whether to enable or disable the alarm output.
For the alarm output function, refer to the following.
Page 193 Alert output function
Setting value
0
1
2
Setting a value other than the above causes an alarm output setting range error (error code: 1B0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alarm output setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Disable (0) for all the channels.
Alarm output setting [FX3 allocation mode]
Set whether to enable or disable disconnection detection or alarm output while the FX3 allocation mode function is in use.
The setting contents in FX3 allocation mode are as follows.
b15 b14 b13 b12 b11 b10 b9
CH4
CH3
Set the following setting values for the bits corresponding to each CH.
Setting value
0000
0001
0010
Setting a value other than the above causes an alarm output setting range error (error code: 1B0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Alarm output setting [in FX3 allocation mode
function]
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Disable (0) for all the channels.
CH1
508
b8
b7
b6
b5
b4
b3
b2
CH2
CH1
CH1
38
Description
Disable
Enabled (no output limit)
Enable (with output limit)
CH2
CH3
708
908
b1
b0
Description
Disable
Enabled (no output limit)
Enable (with output limit)
CH2
CH3
CH4
1108
CH4
APPX
Appendix 8 Buffer Memory Areas