Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 484

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Input type/range setting
This area is for setting an input type and range setting.
Setting value (Hexadecimal)
000FH
0003H
0010H
0006H
0011H
0012H
0000H
0013H
0014H
0015H
0016H
0017H
0018H
0009H
000AH
000BH
A channel where the set value is other than the above causes an input type/range setting range error (error code: 190H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Setting Input type/range
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is conversion disabled (000FH).
APPX
482
Appendix 12 Buffer Memory Areas
Input type
Conversion disable
Current
Voltage
Resistance temperature detector
Thermocouple
CH1
CH2
598
798
Input range
4 to 20 mA
0 to 20 mA
-20 to +20 mA
1 to 5 V
0 to 5 V
-10 to +10 V
0 to 10 V
Pt100
Ni100
Thermocouple B
Thermocouple R
Thermocouple S
Thermocouple K
Thermocouple J
Thermocouple T
CH3
CH4
CH5
998
1198
1398
CH6
CH7
CH8
1598
1798
1998