Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 351

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Ex.
When the input characteristics is adjusted in a channel where the input range of -10 to +10 V is set by the shift function
(+52000)
+32767
+32000
(2)
0
-12000
(1)
-32000
-10
-5
Voltage input (V)
-10
-5
0
+5
+10
*1 Because the value exceeds the range of -32768 to +32767, the value is fixed to +32767 (the upper limit value).
Analog input voltage (V)
0
+5
+10
Digital output value
-32000
-16000
0
+16000
+32000
(1)
'CH1 Digital output value' (Un\G400)
+
'CH1 Conversion value shift amount' (Un\G472)
"+20000"
(2)
'CH1 Digital operation value' (Un\G402)
Digital operation value
-12000
+4000
+20000
*1
+32767
*1
+32767