Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 469

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Warning output function (Process alarm)
Set whether to enable or disable the alert output of the process alarm.
For details on the alert output function, refer to the following.
Page 354 Alert output function
Setting value
0
1
Setting a value other than the above causes an alert output setting (Process alarm) range error (error code: 1B0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alert output setting (Process alarm)
CH Alert output setting (Process alarm) (In FX2N allocation
mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Disable (1).
CH1 Warning output setting (Rate alarm)
Set whether to enable or disable the alert output of the rate alarm.
For details on the alert output function, refer to the following.
Page 354 Alert output function
Setting value
0
1
Setting a value other than the above causes an alert output setting (Rate alarm) range error (error code: 1B8H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alert output setting (Rate alarm)
CH Alert output setting (Rate alarm) (in FX2N allocation
mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Disable (1).
Setting content
Enable
Disable
CH1
CH2
CH3
CH4
512
712
912
1112
1181
1182
1183
1184
Setting content
Enable
Disable
CH1
CH2
CH3
CH4
513
713
913
1113
1211
1212
1213
1214
CH5
CH6
CH7
1312
1512
1712
1185
1186
1187
CH5
CH6
CH7
1313
1513
1713
1215
1216
1217
APPX
Appendix 12 Buffer Memory Areas
CH8
1912
1188
A
CH8
1913
1218
467