Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 448

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Offset/gain setting mode status flag (b10)
When registering the value, which has been adjusted with the offset/gain setting, use as an interlock condition to turn
offonoff 'User range write request' (Un\G70, b10).
'Module READY'
(Un\G69, b0)
'Offset/gain setting mode status
flag'
(Un\G69, b10)
'User range write request'
(Un\G70, b10)
■Channel change completed flag (b11)
When changing a channel to perform the offset/gain setting, use as an interlock condition to turn offonoff 'Channel
change request' (Un\G70, b11).
'CH1 Offset/gain setting mode
(offset specification) (Un\G4132),
'CH1 Offset/gain setting mode
(gain specification) (Un\G4133)
'Channel change completed flag'
(Un\G69, b11)
'Channel change request'
(Un\G70, b11)
APPX
446
Appendix 12 Buffer Memory Areas
Controlled by the multiple input module
Controlled by the program
OFF
ON
ON
OFF
Controlled by the multiple input module
Controlled by the program
Offset setting/gain setting channel
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
OFF

Advertisement