Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 466

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Default value
The default value is off (0).
CH1 Average processing specification
Set which processing is to be used, sampling processing or averaging processing.
Averaging processing consists of time average, count average, and moving average.
Setting value
0
1
2
3
Setting a value other than the above causes an averaging process specification setting range error (error code: 191H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Averaging process specification
CH Averaging process specification (In FX2N allocation
mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Sampling processing (0).
CH1 Time Average/Count Average/Moving Average
Configure the time (for averaging), count (for averaging), and moving average count for each channel where the averaging
processing is specified.
The following table lists the setting ranges.
Setting content
Time average
Count average
Moving average
Setting a value other than the above causes any of time average setting range error (error code: 192H),
count average setting range error (error code: 193H), moving count setting range error (error code:
194H), and the conversion processing is executed with the setting before error.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Time Average/Count Average/Moving Average setting
CH Time average/Count average/Moving average setting (In
FX2N allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
APPX
464
Appendix 12 Buffer Memory Areas
Setting content
Sampling processing
Time average
Count average
Moving average
CH1
CH2
CH3
501
701
901
1081
1082
1083
Setting value
When the input type is current, and voltage: 4 to 10000 (ms)
When the input type is resistance temperature detector, and thermocouple: 160 to 10000
(ms)
4 to 10000 (times)
2 to 1000 (times)
CH1
CH2
CH3
502
702
902
2
3
4
CH4
CH5
CH6
1101
1301
1501
1084
1085
1086
CH4
CH5
CH6
1102
1302
1502
5
6
7
CH7
CH8
1701
1901
1087
1088
CH7
CH8
1702
1902
8
9

Advertisement

Table of Contents
loading

Table of Contents