Advertisement

CH1 Maximum value
The maximum value of the digital operation value is stored in 16-bit signed binary value.
b15 b14 b13 b12 b11 b10 b9
(2)
(1) Data section
(2) Sign bit 0: Positive, 1: Negative
In the following cases, 'CH1 Maximum value' (Un\G404) is updated with the current value.
• When 'Operating condition setting request' (Un\G70, b9) is turned offonoff, and the setting is changed
• When 'CH1 Maximum value reset request' (Un\G473) is turned offonoff
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Maximum value
CH Maximum value (In FX2N allocation mode function)
■Refreshing cycle
The value is updated every conversion cycle.
• For the channel to which the averaging processing is specified, the maximum and minimum values are
stored at every averaging processing time.
• When the scaling function, shift function, and digital clipping function are used, values calculated by each
function are stored in Maximum value and Minimum value.
CH1 Minimum value
The minimum value of the digital operation value is stored in 16-bit signed binary value.
b15 b14 b13 b12 b11 b10 b9
(2)
(1) Data section
(2) Sign bit 0: Positive, 1: Negative
In the following cases, 'CH1 Minimum value' (Un\G406) is updated with the current value.
• When 'Operating condition setting request' (Un\G70, b9) is turned offonoff, and the setting is changed
• When 'CH1 Minimum value reset request' (Un/G474) is turned offonoff
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Minimum value
CH Minimum value (In FX2N allocation function mode)
■Refreshing cycle
The value is updated every conversion cycle.
• For the channel to which the averaging processing is specified, the maximum and minimum values are
stored at every averaging processing time.
• When the scaling function, shift function, and digital clipping function are used, values calculated by each
function are stored in Maximum value and Minimum value.
APPX
452
Appendix 12 Buffer Memory Areas
b8
b7
b6
b5
b4
b3
b2
(1)
CH1
404
111
b8
b7
b6
b5
b4
b3
b2
(1)
CH1
406
101
b1
b0
CH2
CH3
CH4
604
804
1004
112
113
114
b1
b0
CH2
CH3
CH4
606
806
1006
102
103
104
CH5
CH6
CH7
1204
1404
1604
115
116
117
CH5
CH6
CH7
1206
1406
1606
105
106
107
CH8
1804
118
CH8
1806
108

Advertisement

Table of Contents
loading

Table of Contents