Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 478

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Logging data setting
Determine the target to be collected: digital output value or digital operation value.
For details on the logging function, refer to the following.
Page 371 Logging function
Setting value
0
1
Setting a value other than the above causes a logging data setting range error (error code: 1D3H).
When 'CH1 Logging enable/disable setting' (Un\G535) is set to Disable (1), the setting for 'CH1 Logging data setting'
(Un\G536) is ignored.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging data setting
CH Logging data setting (in FX2N allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Digital operation value (1).
CH1 Logging cycle setting value
Set a cycle for storing the logging data.
For details on the logging function, refer to the following.
Page 371 Logging function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Logging cycle setting value
CH Logging cycle setting value (In FX2N allocation mode
function)
■Setting range
The setting range varies depending on the setting in 'CH1 Logging cycle unit setting' (Un\G538) and 'CH1 Input type/range
setting' (Un\G598).
CH1 Logging cycle unit setting (Un\G538)
ms (1)
s (2)
• Setting a value out of the above range causes a logging cycle setting value range error (error code: 1D1H). Logging
cannot be performed.
• If the set logging cycle is below the update cycle of data to be logged, a logging cycle setting disable error (error code:
1D2H) occurs. Logging cannot be performed.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is set to 1.
APPX
476
Appendix 12 Buffer Memory Areas
Setting content
Digital output value
Digital operation value
CH1
CH2
536
736
9171
9172
CH1
CH2
537
737
9181
9182
CH1 Input type/range setting (Un\G598)
Current/Voltage
Resistance temperature detector/thermocouple
CH3
CH4
CH5
936
1136
1336
9173
9174
9175
CH3
CH4
CH5
937
1137
1337
9183
9184
9185
Setting range
1 to 32767
40 to 32767
1 to 3600
CH6
CH7
CH8
1536
1736
1936
9176
9177
9178
CH6
CH7
CH8
1537
1737
1937
9186
9187
9188