Warning output flag (Rate alarm upper limit)
The upper limit alarm of the rate alarm can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Rate alarm upper limit)
■Alert output flag status
• If the limit specified in the rate alarm upper limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert output flag
(Rate alarm upper limit)' (Un\G38) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting (Rate
alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■Clearing Alert output flag
• When the digital output value becomes smaller than the rate alarm upper limit value, the flag is automatically cleared.
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Warning output flag (Rate alarm lower limit)
The lower limit alarm of the rate alarm can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Rate alarm lower limit)
■Alert output flag status
• When the value becomes equal to or smaller than the range specified in the rate alarm lower limit value, Alarm ON (1) is
stored in 'Alert output flag (Rate alarm lower limit)' (Un\G39) corresponding to each channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting (Rate
alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■Clearing Alert output flag
• When the digital output value becomes smaller than the rate alarm lower limit value, the flag is automatically cleared.
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
38
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
39
b1
b0
CH1
CH2
CH3
CH4
b1
b0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH5
CH6
CH7
APPX
Appendix 12 Buffer Memory Areas
CH8
A
CH8
439