Detection method
One of the following detection methods can be selected.
Detection method
0: Disable
1: Upper and lower limit
detection
2: Lower limit detection
3: Upper limit detection
4: Simple disconnection
detection
3 FX5-8AD
362
3.4 Functions
Detection condition
Input signal errors are not detected.
An input signal error is detected when the
analog input value is equal to or greater
than the input signal error detection upper
limit value, or when the analog input value
is equal to or smaller than the input signal
error detection lower limit value.
An input signal error is detected when the
analog input value is equal to or smaller
than the input signal error detection lower
limit value.
An input signal error is detected when the
analog input value is equal to or greater
than the input signal error detection upper
limit value.
Simple disconnection detection is performed. For details, refer to the following.
Page 363 Simple disconnection detection
Analog input value
Error
detection
Input signal error
detection upper limit value
Input signal error
detection lower limit value
Error
detection
Analog input value
No error
detection
Input signal error
detection upper limit value
Input signal error
detection lower limit value
Error
detection
Analog input value
Error
detection
Input signal error
detection upper limit value
Input signal error
detection lower limit value
No error
detection
Time (t)
Time (t)
Time (t)