CH1 Rate alarm alert detection cycle setting
Set the cycle to detect the change amount of digital output values.
The value of the cycle to detect a rate alarm alert is the product of the value in 'CH1 Rate alarm alert detection cycle setting'
(Un\G522) and the conversion cycle.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Rate alarm alert detection cycle setting
CH Rate alarm alert detection cycle setting (In FX2N
allocation mode function)
■Setting range
The possible setting range is from 1 to 32000 (times).
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is set to 0.
• A channel where the set value is out of the range causes a rate alarm detection cycle setting range error
(error code: 1B9H).
• Since the default value is 0, change the setting value when setting the rate alarm function.
CH1 Rate alarm upper limit value
Set an upper limit value of the change rate of digital operation values to detect a rate alarm.
For details on the alert output function, refer to the following.
Page 354 Alert output function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Rate alarm upper limit value
CH Rate alarm upper limit value (In FX2N allocation mode
function)
■Setting range
The possible setting range is from -32768 to +32767.
Unit of the setting value differs depending on the setting of 'Rate alarm change rate selection' (Un\G299).
Rate alarm change rate selection (Un\G299)
Rate specification (0)
Digital output value specification (1)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is set to 0.
APPX
470
Appendix 12 Buffer Memory Areas
CH1
CH2
CH3
522
722
922
1221
1222
1223
CH1
CH2
CH3
524
724
924
91
92
93
Unit
0.1%
digit
CH4
CH5
CH6
1122
1322
1522
1224
1225
1226
CH4
CH5
CH6
1124
1324
1524
94
95
96
CH7
CH8
1722
1922
1227
1228
CH7
CH8
1724
1924
97
98

Advertisement

Table of Contents
loading

Table of Contents