CH1 Time average/Count average/Moving average/Primary delay filter constant setting
Configure the time (for averaging), count (for averaging), moving average count, and Primary delay filter constant for each
channel where the averaging processing is specified.
The following table lists the setting ranges.
Setting value
2 to 5000 (ms)
4 to 62500 (counts)
2 to 1000 (counts)
1 to 500 (times)
Setting a value other than the above causes any of time average setting range error (error code: 192H), count average
setting range error (error code: 193H), moving count setting range error (error code: 194H), Primary delay filter range
error (error code: 195H), and the A/D conversion processing is executed with the setting before error.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Time average/Count average/Moving
average/Primary delay filter constant setting
CH Time average/Count average/Moving
average/Primary delay filter constant setting (in
FX3 allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 0 for all channels.
• Set a Primary delay filter constant for the Primary delay filter. The value of the time constant (ms) is the
product of the Primary delay filter constant and the conversion cycle.
• Since the default value is 0, change the setting value according to the processing method.
• The setting for this area is ignored in the channel where Digital filter (5) is set to 'CH1 Averaging process
specification' (Un\G501).
CH1 Scaling enable/disable setting
Set whether to enable or disable the scaling.
For details on the scaling function, refer to the following.
Page 34 Scaling function
Setting value
0
1
Setting a value other than the above causes a scaling enable/disable setting range error (error code: 1A0H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Scaling enable/disable setting
CH Scaling enable/disable setting (In FX3
allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
APPX
154
Appendix 4 Buffer Memory Areas
Setting content
Time average
Count average
Moving average
Primary delay filter constant
CH1
CH2
502
702
2
3
Setting content
Enable
Disable
CH1
CH2
504
704
1091
1092
CH3
CH4
902
1102
4
5
CH3
CH4
904
1104
1093
1094