Error code
Error name
1E6H
User range data invalid (CH
specification enable)
1E7H
Offset/gain value inversion
error
1E8H
Offset/gain setting channel
range error
1E9H
Offset/gain setting range
range error
1F08H
Module power supply error
3001H
Hardware failure
3030H
Flash memory error
Description and cause
An invalid value is set in CH Offset/gain setting.
The offset value and gain value to be saved in the
flash memory are as follows:
Offset value Gain value
A value other than 0 and 1 is set in CH Offset/gain
setting mode (offset specification) and CH Offset/
gain setting mode (gain specification).
When the offset and gain are set, values other than
D or E were set in 'CH Offset/gain setting mode'
(range specification).
The 24 V DC power supply is not normally supplied
to the module.
A hardware failure in the module.
The data in the flash memory is abnormal.
Corrective action
Perform the offset/gain setting again for the
channels where the error has occurred.
If the error occurs again, the possible cause is a
failure of the module. Please consult your local
Mitsubishi representative.
Perform the offset/gain setting again so that the
following condition is satisfied:
Offset value < Gain value
Set CH Offset/gain setting mode (offset
specification) and CH Offset/gain setting
mode (gain specification) to 0 or 1.
Retry to set the 'CH Offset/gain setting mode'
(range specification) to D or E.
Check the wiring of the cable or the supplied
voltage.
After the check, turn offonoff Error clear
request (Un\G70, b15) to eliminate this error
and resume the conversion.
If the error occurs again, the possible cause is a
failure of the module. Please consult your local
Mitsubishi representative.
Power offon the module.
If the error occurs again, the possible cause is a
failure of the module. Please consult your local
Mitsubishi representative.
Check the analog output values.
If the values are abnormal, please consult your
local Mitsubishi representative.
2 FX5-4DA
2.10 Troubleshooting
2
275