Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 297

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Alarm output flag (upper/lower limit)
When the FX3 allocation mode function is used, the upper/lower limit alarm can be checked.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Alarm output flag (upper/lower limit) (in FX3
allocation mode function)
■Alarm output flag status
• When the value is out of the range specified in the alert output upper limit value or alert output lower limit value, Alert alarm
ON (1) is stored in 'Alarm output flag' (Un\G48) corresponding to each channel.
• When an alert is detected in any channel where the D/A conversion and the alert output setting are enabled, 'Alarm output
signal' (Un\G69, b14) also turns on.
■Clearing Alarm output flag
Turn on and off 'Operating condition setting request' (Un\G70, b9) or 'Alarm output clear request' (Un\G70, b14).
Disconnection detection flag
By setting 4 to 20 mA, 0 to 20 mA, or user range (current) for the analog output range and enabling the D/A conversion, a
disconnection can be detected for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Disconnection detection
(2) b4 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Disconnection detection flag
Disconnection detection flag (in FX3 allocation
mode function)
■Status of Disconnection detection flag
• When a disconnection is detected, Disconnection detection (1) is stored in 'Disconnection detection flag' (Un\G38)
corresponding to each channel.
• When a disconnection is detected in any channel, 'Disconnection detection signal' (Un\G69, b13) turns on.
■Clearing disconnection detection flag
Even if the disconnection cause is eliminated from the disconnected state when the disconnection detection auto-clear
enable/disable setting is disabled, analog output does not restart automatically to prevent an incorrect output.
To restart analog output, perform the following. Analog output restarts according to the state of CH Output enable/disable
flag (Un\G70, b1 to 4).
• In the normal output mode
Check the CH Digital value, and then turn on and off 'Error clear request' (Un\G70, b15).
• In the wave output mode
b8
b7
b6
b5
b4
b3
b2
CH4 CH4
CH3
CH3
CH2
CH2 CH1
Upper
Lower
Upper
Lower
Upper
Lower
0
limit
limit
limit
limit
limit
limit
value
value
value
value
value
value
(1)
CH1
39
b8
b7
b6
b5
b4
b3
b2
0
0
0
0
0
CH4
CH3
CH2
(1)
CH1
38
28
b1
b0
CH1
Upper
Lower
limit
limit
value
value
CH2
CH3
b1
b0
CH1
CH2
CH3
CH4
CH4
APPX
Appendix 8 Buffer Memory Areas
A
295

Advertisement

Table of Contents
loading

Table of Contents