Logging cycle
■Logging cycle setting
Set the logging cycle with 'CH1 Logging cycle setting value' (Un\G537) and 'CH1 Logging cycle unit setting' (Un\G538).
The following table lists the setting range for each cycle.
Setting value of CH1 Logging cycle unit setting
s (0)
ms (1)
s (2)
The logging cycle must be an integral multiple of the conversion cycle. Even if the setting is not an integral multiple, the actual
logging cycle is adjusted to the integral multiple of the conversion cycle within a limit of the set logging cycle.
The following table lists the conversion cycle for each A/D conversion method.
Conversion method
Conversion cycle
Number of conversion enabled channels  Conversion speed
Sampling processing
Time average
Moving average/Primary delay filter constant setting
Number of conversion enabled channels × Conversion speed
The count set to CH1 Time average/Count average/Moving average/Primary delay filter constant setting (Un\G502))  (Number of
Count average
A/D conversion enabled channels  Conversion speed
Number of A/D conversion enabled channels  Conversion speed
Moving average
Number of A/D conversion enabled channels  Conversion speed
Primary delay filter
Digital filter
For details, refer to the following.
Page 31 Digital filter
*1 Values after the decimal point are omitted.
Ex.
With the following settings, the conversion cycle is 320 s and the actual logging cycle is 9.92 ms (integral multiple of 320 s).
Item
Conversion enabled channels
Averaging process specification
Logging cycle setting value
Logging cycle unit setting
The following values are stored in 'CH1 Logging cycle monitor value' (Un\G441 to Un\G443).
Address
441
442
443
■When the logging function becomes disabled
The logging is not performed when one of the following errors occurs after the logging function is enabled and 'Operating
condition setting request' (Un\G70, b9) is offonoff.
• Error code (191H): Setting errors of 'CH1 Averaging process specification' (Un\G501)
• Error code (192H to 195H): Setting errors of 'CH1 Time average/Count average/Moving average/Primary delay filter
constant setting' (Un\G502)
• Error code (19DH): Setting error of 'CH1 Digital filter setting' (Un\G570)
• Error code (19EH): Setting error of 'CH1 Digital filter fluctuation width setting' (Un\G572, Un\G573)
• Error code (1D0H to 1D6H): Setting errors of the logging function
• Error code (1D8H, 1D9H): Setting errors of the logging read function
Time set in Time average/Count average/
Item
CH1 Logging cycle monitor value (Un\G441 to Un\G443)
Setting range of CH1 Logging cycle setting value
80 to 32767
1 to 32767
1 to 3600
*1
× Number of A/D conversion enabled channels
× Conversion speed
Setting
CH1 to CH4
Sampling processing
10
ms
Stored value
0 (s)
9 (ms)
920 (s)
1 FX5-4AD
1.4 Functions
1
61