■Changing the module settings
For the wave output function parameter settings written with the program, 'Operating condition setting request' (Un\G70, b9)
needs to be turned offonoff to enable the settings. When the settings are enabled, the CH1 Analog output value set as D/
A conversion enable changes to the following depending on the status of the 'CH1 Output enable/disable flag' (Un\G70, b1).
• 'CH1 Output enable/disable flag' (Un\G70, b1) Changes to the offset value.
• 'CH1 Output enable/disable flag' (Un\G70, b1) The setting in 'CH1 Output setting during wave output stop' (Un\G524) is
output.
CPU module status
CH1 D/A conversion enable/disable
setting (Un\G500)
CH1 Output enable/disable flag
(Un\G70, b1)
Output value as per the setting of CH1 Output
setting during wave output stop (Un\G524)
Offset value
Set the CH1 D/A conversion enable/disable setting (Un\G500) to D/A conversion enable (0) and turn offonoff 'Operation condition setting request'
(Un\G70, b9).
Set the CH1 D/A conversion enable/disable setting (Un\G500) to D/A conversion disable (1) and offonoff 'Operation condition setting request'
(Un\G70, b9).
When the wave output function is in use, the parameter setting can be enabled by turning offonoff
'Operating condition setting request' (Un\G70, b9) only when all channels are at a wave output stop (the CH
Wave output status monitors for all channels are at a wave output stop (0)).
An alarm will occur if 'Operating condition setting request' (Un\G70, b9) is turned offonoff when the wave
output status is other than the wave output stopped state for even one channel. Alarm code 0B0H is stored
in 'Latest alarm code' (Un\G2). The parameter setting will not be enabled.
RUN
D/A conversion disable (1)
D/A conversion enable (0)
OFF
Analog output
0 V/0 mA
D/A conversion disable (1)
ON
2
2 FX5-4DA
213
2.4 Functions