Offset/Gain Initialization Function - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Ex.
When the 17th error occurs:
The 17th error is stored in Error history No. 1, and the value 3600 (start address of Error history No. 1) is stored to Latest
address of error history.
'Latest address of error history'
(Un\G1): 3600
• Once the error history storage area becomes full, subsequent error information will overwrite the existing
data, starting from Error history 1 (Un\G3600 to Un\G3609), and continues sequentially thereafter. The
overwritten history is deleted.
• The same processing is performed for Alarm history when an alarm occurs.
• The stored error history is cleared when a multiple input module is powered off or the CPU module is reset.

Offset/gain initialization function

Offset/gain initialization
The offset and gain values are initialized to the factory default offset and gain values according to the set input type.
1.
Set the mode to the "Normal mode".
2.
Set 'CH1 Input type/Range setting'(Un\G598) to 'CH8 Input type/Range setting' (Un\G1998) as 'Conversion disabled' and
turn offonoff 'Operation condition setting request' (Un\G70, b9).
3.
Set "E20FH" to 'Offset/gain initialization enabled code' (Un\G305).
4.
Turn ON (1) 'Offset/gain initialization request' (Un\G70, b5).
Precautions
Channels for which the offset and gain have not been set are initialized with the current range.
3 FX5-8AD
386
3.4 Functions
Un\G3600
Error history 1
1st error
Un\G3610
Error history 2
2nd error
Un\G3620
Error history 3
3rd error
Un\G3750
Error history 16
16th error
Latest
17th error