Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 172

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

CH1 Range setting
This area is for setting an input range.
Setting value
0003H
0009H
0006H
000AH
000BH
0000H
000CH
000EH
Setting a value other than the above causes an input range setting range error (error code: 190H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Range setting
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 0003H for all channels.
Range setting [FX3 allocation mode]
When the FX3 allocation mode function is used, this area is for setting an input range.
Range setting (Un\G0)
(Setting range CH1 to CH4)
Set the following setting values for the bits corresponding to each CH.
Setting value
0H
1H
2H
3H
4H
5H
6H
7H
8H
9H
AH
BH
CH
EH
■Buffer memory address
Buffer memory name
Range setting (in FX3 allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
APPX
170
Appendix 4 Buffer Memory Areas
CH1
598
b15
...
b12 b11
...
CH4
CH3
CH1
0
Input range
4 to 20 mA
0 to 20 mA
-20 to +20 mA
1 to 5 V
0 to 5 V
-10 to +10 V
0 to 10 V
User range setting
CH2
798
b8 b7
...
b4
b3
CH2
CH1
(1)
Input range
-10 to +10 V
4 to 20 mA
-20 to +20 mA
0 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
User range setting
CH2
CH3
CH4
998
1198
...
b0
CH3
CH4