External wiring example
The followings show the examples of external wiring.
Voltage input, and current input
24 V DC
Grounding
(Grounding resistance: 100 or less)
CH
Shielded wire
For in CH, the CH number is entered.
Precautions
Use a two-conductor shielded twisted pair cable for analog input lines and carry out the wiring while separating them from
other power lines and lines susceptible to induction.
Thermocouple
Refer to Page 330 Thermocouple input specifications for the thermocouples that can be used with multiple input module.
24 V DC
Grounding
(Grounding resistance: 100 or less)
Compensating conductor
(shielded wire)
For in CH, the CH number is entered.
Precautions
When using thermocouple input, use the prescribed compensation lead wire.
Use insulated thermocouple types.
Case of RTD
Refer to Page 330 Resistance temperature detector (RTD) input specifications for the resistance temperature detector
that can be used with multiple input module.
24 V DC
Grounding
(Grounding resistance: 100 or less)
Shielded wire
For in CH, the CH number is entered.
Precautions
When using the resistance temperature detector, carry out the wiring with a wire with low lead wire resistance and no
resistance difference between the lead wires.