Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 211

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Initializing the wave output function
For the wave output function, the following are required to be initialized. Before executing the wave output function, perform
the settings described in this section.
• Register the wave pattern (Page 250 Register the wave pattern)
• Create the wave output function parameters (Page 254 Setting the wave output function parameters)
• Save the wave pattern (Page 254 Save the wave pattern)
• Parameter setting of the analog output module (Page 209 Parameter setting of the analog output module)
■Parameter setting of the analog output module
When the wave output function is to be used, the module parameters need to be set up separately from setting up the wave
output function parameters.
The items to be with the module parameters are as follows.
• Output range setting
Same as normal output. Select the output range to be used.
Note that when the wave output function is in use, no user range is available.
• Operation mode setting
Select "Normal mode" for the operation mode setting.
• Output mode setting
Select "Wave output mode" for the output mode setting.
• Analog output HOLD/CLEAR setting
The analog output HOLD/CLEAR function differs from operation from that for normal output. For the differences in operation
arising from the HOLD/CLEAR setting, refer to the following.
Page 186 Analog output HOLD/CLEAR function
• Disconnection detection auto-clear enable/disable setting
"Disconnection detection auto-clear enable/disable setting" cannot be used.
2
2 FX5-4DA
209
2.4 Functions