Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 62

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Operation of logging
■Starting logging data collection
Logging data collection starts when 'CH1 Logging enable/disable setting' (Un\G535) is set to Enable (0) and 'Operating
condition setting request' (Un\G70, b9) is turned offonoff.
The data in 'CH1 Digital output value' (Un\G400) or 'CH1 Digital operation value' (Un\G402) is stored in CH1 Logging data
(Un\G10000 to Un\G19999) on the set logging cycle.
'CH1 Logging enable/disable setting'
(Un\G535)
'Operating condition setting request'
(Un\G70, b9)
'Operating condition setting completed
flag' (Un\G69, b9)
■Logging data
Logging data are stored in the following buffer memory areas.
When the number of stored data points is 1001 or greater, the data is overwritten with new data from the head of the storage
area of the corresponding channel.
Channel
CH1
CH2
CH3
CH4
If logging has been performed even once, all the logging data above are cleared to 0 at the timing when 'Operating condition
setting request' (Un\G70, b9) is turned offon.
Logging data setting
Select a data type to be collected with 'CH1 Logging data setting' (Un\G536).
• Digital output value (0)
• Digital operation value (1)
1 FX5-4AD
60
1.4 Functions
Disable
Enable (0)
(1)
ON
OFF
ON
ON
OFF
Logging starts.
Storage area for logging data
Un\G10000 to Un\G19999
Un\G20000 to Un\G29999
Un\G30000 to Un\G39999
Un\G40000 to Un\G49999

Advertisement

Table of Contents
loading

Table of Contents