Warning output flag (Process alarm upper limit)
The upper limit alarm of the process alarm can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) The values of b4 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Process alarm upper limit)
■Alert output flag status
• If the limit specified by the process alarm upper upper limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert
output flag (Process alarm upper limit)' (Un\G36) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■Clearing Alert output flag
• When the digital operation value returns within the setting range, the flag is automatically cleared.
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Warning output flag (Process alarm lower limit)
The lower limit alarm of the process alarm can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) The values of b4 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Process alarm lower limit)
■Alert output flag status
• If the limit specified by the process alarm lower lower limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert
output flag (Process alarm lower limit)' (Un\G37) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■Clearing Alert output flag
• When the digital operation value returns within the setting range, the flag is automatically cleared.
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
b8
b7
b6
b5
b4
b3
b2
0
0
0
0
0
CH4
CH3
CH2
(1)
CH1
36
b8
b7
b6
b5
b4
b3
b2
0
0
0
0
0
CH4
CH3
CH2
(1)
CH1
37
b1
b0
CH1
CH2
CH3
b1
b0
CH1
CH2
CH3
CH4
CH4
APPX
Appendix 4 Buffer Memory Areas
A
125