Digital Clipping Function - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Digital clipping function

Fixes a possible digital operation value to the maximum digital output value or the minimum digital output value when an input
current or voltage exceeds the input range.
List of output ranges
The following table lists the output ranges of the digital operation values when the digital clipping function is enabled with each
range.
Input range
4 to 20 mA
0 to 20 mA
1 to 5 V
0 to 5 V
0 to 10 V
-20 to +20 mA
-10 to +10 V
When the determined digital operation value is out of the range of -32768 to +32767, the digital clipping
function is performed to the following values.
• When 32767 or greater: 32767
• When -32768 or smaller: -32768
Setting procedure
Set "Digital clipping enable/disable setting" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter]
[Application setting]  [Digital clipping function]
Output range of digital operation values
Digital clipping function is enabled
0 to 32000
-32000 to +32000
Digital clipping function is disabled
-768 to +32767
-32768 to +32767
3 FX5-8AD
3.4 Functions
3
351

Advertisement

Table of Contents
loading

Table of Contents