CH1 Alert output setting (Rate alarm)
Set whether to enable or disable the alert output of the rate alarm.
For details on the alert output function, refer to the following.
Page 46 Alert output function
Setting value
0
1
Setting a value other than the above causes an alert output setting (Rate alarm) range error (error code: 1B8H).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Alert output setting (Rate alarm)
CH Alert output setting (Rate alarm) (in FX3
allocation mode function)
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is Disable (1) for all channels.
CH1 Process alarm upper upper limit value
Set an upper upper limit value of the alert output function (Process alarm).
For details on the alert output function, refer to the following.
Page 46 Alert output function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Process alarm upper upper limit value
CH Process alarm upper upper limit value (in
FX3 allocation mode function)
■Setting range
The possible setting range is from -32768 to +32767.
■Enabling the setting
Turn offonoff 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 0 for all channels.
Setting content
Enable
Disable
CH1
CH2
513
713
1211
1212
CH1
CH2
514
714
81
82
CH3
CH4
913
1113
1213
1214
CH3
CH4
914
1114
83
84
Appendix 4 Buffer Memory Areas
A
APPX
157