The user range cannot be used when the wave output function is used. Even within the setting range in the above table, when
the user range is set while the wave output function is used, a user range specification error in wave output mode (error code:
1D1H) occurs and the wave output does not start.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Range setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
Error history
Up to 16 errors that occurred in the analog output module are logged.
to
b15
Un\G3600
Un\G3601
First two digits of the year
Un\G3602
Month
Un\G3603
Hour
Second
Un\G3604
Un\G3605
Millisecond (upper)
Un\G3606
to
Un\G3609
Item
First two digits of the year/Last two digits
of the year
Month/Day
Hour/Minute
Second
Day of the week
Millisecond (upper)
Millisecond (lower)
*1 These values assume that an error occurs at 10:35 and 40.628 seconds on Monday, January 30th, 2017.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
Error history
Error history (In FX3 allocation mode function)
CH1
CH2
0
b8 b7
to
Error code
Last two digits of the year
Day
Minute
Day of the week
Millisecond (lower)
System area
Storage contents
Stored in BCD code.
One of the following values is stored in BCD code.
Sunday: 0, Monday: 1, Tuesday: 2, Wednesday: 3, Thursday: 4, Friday: 5, Saturday: 6
Stored in BCD code.
No.1 to No.16
3600 to 3759
8600 to 8759
CH3
b0
Appendix 8 Buffer Memory Areas
CH4
*1
Storage example
2017H
0130H
1035H
40H
A
1H
6H
28H
APPX