■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 10000 for all channels.
CH1 Wave pattern data points setting
This area is for setting the data points of the wave pattern to be output when the wave output function is used.
The setting for this area is enabled only in the wave output mode. In other modes, changing the setting value is ignored.
In the channel where the set values in this area and in 'CH1 Wave pattern data points setting' (Un\G528, Un\G529) satisfy the
following conditions, a wave data registry area range error (error code: 1D9H) occurs and 'Error flag' (Un\G69, b15) turns
on. The wave output does not start.
(Wave pattern start address setting + Wave pattern data points setting - 1) > 89999 (the last buffer memory address of the
wave data registry area)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave pattern data points setting
CH Wave pattern data points setting (in FX3
allocation mode function)
■Setting range
The setting range is from 1 to 80000 (the number of data points of the wave data registry area).
In the channel where a value out of the setting range is set, a wave pattern data points setting range error (error code:
1D5H) occurs and 'Error flag' (Un\G69, b15) turns on. The wave output does not start.
However, when the value of 'CH1 Wave pattern start address setting' (Un\G526, Un\G527) is out of the setting range, the
above error does not occur.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■Default value
The default value is 0 for all channels.
CH1 Wave pattern output repetition setting
This area is for setting the number of wave pattern outputs when the wave output function is used.
The setting for this area is enabled only in the wave output mode. In other modes, changing the setting value is ignored.
Setting value
-1
1 to 32767
In the channel where a value out of the setting range is set, a wave pattern output repetition setting range error (error code:
1D6H) occurs and 'Error flag' (Un\G69, b15) turns on. The wave output does not start.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave pattern output repetition setting
CH Wave pattern output repetition setting (in
FX3 allocation mode function)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
APPX
320
Appendix 8 Buffer Memory Areas
CH1
CH2
528, 529
728, 729
9200, 9201
9202, 9203
Description
The wave pattern is output in analog unlimitedly.
The wave pattern is output in analog for the set number.
CH1
CH2
530
730
9221
9222
CH3
CH4
928, 929
1128, 1129
9204, 9205
9206, 9207
CH3
CH4
930
1130
9223
9224

Advertisement