■Clearing Input signal error detection flag
Clearing input signal errors detection flag differs depending on Input signal error detection/disconnection detection auto-clear
enable/disable setting.
When Input signal error detection/disconnection detection auto-clear enable/disable setting is set to Enable (0)
• When an analog input value falls within the normal range, Normal (0) is stored in the corresponding bit of 'Input signal error
detection flag' (Un\G40).
When Input signal error/disconnection detection auto-clear enable/disable setting is set to Disable (1)
• When an analog input value falls within the normal range, if turning offonoff 'Error clear request' (Un\G70, b15), Normal
(0) is stored in the corresponding bit of 'Input signal error detection flag' (Un\G40).
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Disconnection detection flag
The status of disconnection can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Disconnection detection
(2) The values of b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Disconnection detection flag
■Status of Disconnection detection flag
• If a disconnection is detected by the disconnection detection function, disconnection detection flag, which corresponds to
the channel where the disconnection is detected, turns to disconnection detection (1).
• If an error is detected even in one channel, of the channels where conversion is enabled and disconnection detection is
enabled, 'Disconnection detection signal' (Un\G69, b6) turns on.
■Clearing disconnection detection flag
Clearing disconnection detection flag differs depending on Input signal error detection/disconnection detection auto-clear
enable/disable setting.
When Input signal error detection/disconnection detection auto-clear enable/disable setting is set to Enable (0)
• When the disconnection cause is eliminated, and the analog input value falls within the normal range, Normal (0) is stored
in the corresponding bit of 'Disconnection detection flag' (Un\G41).
When Input signal error/disconnection detection auto-clear enable/disable setting is set to Disable (1)
• When an analog input value falls within the normal range, if turning offonoff 'Error clear request' (Un\G70, b15), Normal
(0) is stored in the corresponding bit of 'Disconnection detection flag' (Un\G41).
• Turning offonoff 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Input signal error detection flag/disconnection detection flag [FX2N allocation mode]
The status of an analog input value or disconnection can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
CH8 CH8
CH7
CH7
CH6
CH6 CH5
(1) 0: Normal, 1: Detection
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
41
b8
b7
b6
b5
b4
b3
b2
CH5
CH4 CH4
CH3
CH3
CH2
CH2 CH1
(1)
b1
b0
CH1
CH2
CH3
CH4
b1
b0
CH1
CH5
CH6
CH7
APPX
Appendix 12 Buffer Memory Areas
CH8
A
441

Advertisement

Table of Contents
loading

Table of Contents