Ex.
When the following values are used for multiple input module with the input range of 0 to 5 V
Item
'CH1 Scaling enable/disable setting' (Un\G504)
'CH1 Scaling upper limit value' (Un\G506)
'CH1 Scaling lower limit value' (Un\G508)
'CH1 Conversion value shift amount' (Un\G472)
32000
14000
12000
(3)
4000
2000
0
0
Voltage input (V)
0
1
2
3
4
5
When the shift function is used with the digital clipping function and scaling function, shift-and-add is
performed on the value obtained after digital clipping and scale conversion. Therefore, the range of the digital
operation value is determined as -32768 to +32767.
For a setting example of when the digital clipping function, scaling function, and shift function are used
together, refer to the following.
Page 352 Setting example
3 FX5-8AD
350
3.4 Functions
(1)
(2)
Analog input voltage (V)
5
Digital output value
0
6400
12800
19200
25600
32000
Setting
Enable (0)
12000
2000
2000
(1)
'CH1 Digital output value' (Un\G400)
Scaling
0 to 32000
2000 to 12000
(2)
Value after scaling
'CH1 Conversion value shift amount' (Un\G472) "+2000"
(3)
'CH1 Digital operation value' (Un\G402)
Value after scaling
2000
4000
6000
8000
10000
12000
Digital operation value
4000
6000
8000
10000
12000
14000