Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 54

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

■Setting procedure
1.
Set "Warning output setting (Rate alarm)" to "Enable".
[Navigation window]  [Parameter]  [Module Information]  Module model name  [Module Parameter] 
[Application setting]  [Warning output function (Rate alarm)]
2.
Set "Rate alarm change rate selection".
Item
Rate alarm change rate selection
3.
Set values for "Rate alarm upper limit value" and "Rate alarm lower limit value".
The rate input and the digital output value input vary depending on the rate alarm change rate selection.
• When the rate alarm change rate selection is "Rate specification"
Set it in increments of 0.1% for the width of the analog input range (gain value - offset value).
Item
Rate alarm upper limit value
Rate alarm lower limit value
• When 'Rate alarm change rate' is "Digital output value specification"
Set a value for the range of the digital output value in increments of 1 digits.
Item
Rate alarm upper limit value
Rate alarm lower limit value
Set values within the range satisfying the condition "Rate alarm upper limit value > Rate alarm lower limit
value".
If a value out of the range is set, a rate alarm upper/lower limit setting value inversion error (error code:
1BAH) occurs.
4.
Set an alarm detection cycle of rate alarms.
Set the cycle in "Rate alarm detection cycle setting".
Item
Rate alarm alert detection cycle setting
A channel where the set value is out of the above range causes a rate alarm detection cycle setting range
error (error code: 1B9H).
1 FX5-4AD
52
1.4 Functions
Setting range
0: Rate specification
1: Digital output value specification
Setting range
-32768 to +32767 (-3276.8 to +3276.7%)
Setting range
-32768 to +32767
Setting range
1 to 32000 (times)