Mitsubishi Electric MELSEC iQ-F FX5 User Manual page 312

Analog control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

• Wave output pause
The value differs depending on the analog output HOLD/CLEAR setting.
Setting of analog output HOLD/CLEAR function
Previous Value
Setting value
CLEAR
• During wave output step action
Digital value stored in the buffer memory address indicated with 'CH1 Wave output current address monitor' (Un\G436 to
Un\G437)
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave output current digital value monitor
CH Wave output current digital value monitor
(in FX3 allocation mode function)
CH1 Wave output digital value out-of-range address monitor
When the digital value of the output wave data is out of the range, the buffer memory address of the wave data with a value
out of the range can be checked.
Only in the wave output mode, a value is stored in this area. Otherwise, 0 is stored.
When the multiple wave data with a digital input value out of the setting range are detected, only the buffer memory address
of the wave data detected first is stored.
When the first detection of a digital value out of the range occurs in a wave output status other than During wave output stop,
the stored value is updated.
To reset this area, correct the wave data to a value within the available setting range. After that, turn on and off 'Error clear
request' (Un\G70, b15) or 'Operating condition setting request' (Un\G70, b9) to reset this area.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave output digital value out-of-range
address monitor
CH Wave output digital value out-of-range
address monitor (in FX3 allocation mode
function)
CH1 Wave output warning address monitor
The buffer memory address of the wave data where a warning has occurred can be checked.
Only in the wave output mode, a value is stored in this area. Otherwise, 0 is stored.
When a warning has occurred in the multiple wave data, only the buffer memory address of the wave data where the warning
occurred first is stored.
When the first warning occurs in a wave output status other than During wave output stop, the stored value is updated.
To reset this area, correct the wave data to a value within the setting range. After that, turn on and off 'Alert output clear
request' (Un\G70, b14) or 'Operating condition setting request' (Un\G70, b9) to reset this area.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Wave output warning address monitor
CH Wave output warning address monitor (in
FX3 allocation mode function)
APPX
310
Appendix 8 Buffer Memory Areas
Stored value
Digital value stored in the buffer memory address indicated by 'CH1 waveform
output current address monitor' (Un\G436 to Un\G437)
Setting value for 'CH1 HOLD setting value' (Un\G596)
0
CH1
CH2
438
638
9070
9072
CH1
CH2
440, 441
640, 641
9090, 9091
9092, 9093
CH1
CH2
442, 443
642, 643
9110, 9111
9112, 9113
CH3
CH4
838
1038
9074
9076
CH3
CH4
840, 841
1040, 1041
9094, 9095
9096, 9097
CH3
CH4
842, 843
1042, 1043
9114, 9115
9116, 9117

Advertisement