Error code
Error name
1C4H
Disconnection detection error
1D0H
Wave output start/stop setting
range error
1D1H
Wave output mode user range
specification error
1D2H
Output setting during wave
output stop setting range error
1D3H
Output value during wave
output stop range error
1D4H
Wave pattern start address
setting range error
1D5H
Wave pattern number-of-
points setting range error
1D6H
Wave pattern output repetition
setting range error
1D7H
Wave output conversion cycle
setting range error
1D80H
Step action wave output
request range error
1D9H
Wave data registry area range
error
1DA0H
Module extension parameter
acquisition error
1E50H
Offset/gain setting channel
specification error
1E51H
User range data invalid (CH
specification disable)
1E52H
Analog adjustment output out-
of-range error
2 FX5-4DA
274
2.10 Troubleshooting
Description and cause
A disconnection was detected on CH.
A value out of the range was set in 'CH Wave
output start/stop request'.
In the output mode setting, the wave output mode
was selected, and the user range setting was
selected with the output range setting.
'CH Output setting during wave output stop' is set
to a value other than 0 to 2.
'CH Output value during wave output stop' is set
to a value out of the range.
'CH Wave pattern start address setting' is set to a
value out of the setting range.
'CH Wave pattern data points setting' is set to a
value other than 1 to 80000.
'CH Wave pattern output repetition setting' is set
to a value out of the range.
'CH Constant for wave output conversion cycle' is
set to a value other than 1 to 5000.
'Step action wave output request' is set to a value
other than 0 or 1.
The value obtained by subtracting 1 from the sum of
'CH Wave pattern start address setting' and 'CH
Wave pattern data points setting' is set to a value
exceeding 89999 (final buffer memory address of
wave data registry area).
No module extension parameter can be acquired.
• Multiple channels are set simultaneously while
during offset/gain setting.
• In the offset/gain setting, "1: Setting channel" is
set for both CH Offset/gain setting mode (offset
specification) and CH Offset/gain setting mode
(gain specification), or "0: Disable" is set.
An invalid value is set in the offset/gain setting. The
number of the channel in which this error occurs
cannot be identified.
A value other than -3000 to +3000 is set for the
offset/gain adjustment value specification.
Corrective action
Eliminate the cause of the disconnection from
the channel. If the disconnection detection
automatic clear enable/disable setting is
disabled, remove the cause of the
disconnection and then turn offonoff 'Error
Clear Request' (Un\G70, b15)'.
Retry to set 'CH Wave output start/stop
request' to one of the following.
• Wave output stop request (0)
• Wave output start request (1)
• Wave output pause request (2)
• If the wave output function is to be used, retry
to set the output range to a range other than
the user range by using the output range
setting.
• If the user range setting is to be used, retry to
set the output mode setting to the normal
output mode by using the module parameter
setting.
Retry to set 'CH Output setting during wave
output stop' to one of the following.
• 0 V/0 mA (0)
• Offset value (1)
• Output value during wave output stop (2)
Correct 'CH Output value during wave output
stop' to a value within the setting range. The
setting range depends on the output range
setting.
-10 to +10 V: -32768 to +32767
4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, or 0 to
10 V: 0 to 32767
Retry to set 'CH Wave pattern start address
setting' to a value of 10000 to 89999.
Retry to set 'CH Wave pattern data points
setting' to a value of 1 to 80000.
Retry to set 'CH Wave pattern output
repetition setting' to one of the following.
• Indefinite repetitive output (-1)
• Specified-count output (1 to 32767)
Retry to set 'CH Constant for wave output
conversion cycle' to a value of 1 to 7.
Retry to set 0 or 1 'Step action wave output
request'.
Retry to set 'CH Wave pattern start address
setting' and 'CH Wave pattern number-of-
points setting' to values meeting the following
conditions.
"Wave pattern start address setting" + "Wave
pattern data points setting" -1 89999
Write to the CPU module, the module extension
parameter by which the wave output data was
registered. Then, power offon or reset the
CPU module.
Correctly set CH Offset/gain setting mode
(offset specification) and CH Offset/gain
setting mode (gain specification).
Perform the offset/gain setting again for all
channels where the user range is set.
If the error occurs again, the possible cause is a
failure of the module. Please consult your local
Mitsubishi representative.
Retry to set the offset/gain adjustment value
specification to a value of -3000 to +3000.