14 Fuel meter input X75 pin 1 / X75 pin 2

A fuel meter can be connected to acquire the amount of fuel burnt.
The fuel meter function is only available as an alternative to VSD control. If the VSD is
deactivated, a fuel meter can be connected to terminals X75 pin 1 and X75 pin 2.
LMV...
2
1
Bild 338e/1109
Figure 93: Fuel meter input X75

14.1 Configuration of fuel meter

14.1.1 Types of fuel meters

The LMV37.4 is designed for use with fuel meters equipped with a Reed contact. Pulse
frequency at maximum fuel throughput must be below 300 Hz.

14.1.2 Configuration of pulses per volume unit

Depending on the type of fuel meter used, the number of pulses supplied by it per m³ or
l fuel must be parameterized. A maximum of 400 pulses per volume unit can be preset.
The correct amount of fuel is acquired only when this parameter is set.
When the parameter is 0, the fuel meter stops.
No.
Parameter
128
Fuel meter: Pulse valency (pulses / volume unit)

14.1.3 Reading and resetting the meter readings

No.
Parameter
167
Fuel volume resettable (m³, l, ft³, gal)
The cumulated fuel volume can be read out per parameter. The meter reading can also
be reset on the parameter level.
Basic documentation LMV37.4...
14 Fuel meter input X75 pin 1 / X75 pin 2
Fuel meter input
Detector supply fuel meter
CC1P7546en