Line Filter - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Description
3.5 Components for the Power Modules
3.5.2

Line filter

With a line filter, the inverter can achieve a higher radio interference class.
NOTICE
Overloading the line filter when connected to line supplies that are not permissible
The line filter is only suitable for operation on TN or TT line supplies with a grounded neutral
point. If operated on other line supplies, the line filter will be thermally overloaded and will be
damaged.
● For inverters equipped with line filter, only connect to TN or TT line supplies with a
External line filters for PM230, 380 V ... 480 V (IP20)
Power Module
FSA
FSB
FSC
FSD
FSE
FSF
External line filters for PM330, 380 V ... 480 V
Power Module
GX
42
grounded neutral point.
6SL3210‑1NE11‑3UG1,
6SL3210‑1NE11‑7UG1,
6SL3210‑1NE12‑2UG1,
6SL3210‑1NE13‑1UG1,
6SL3210‑1NE14‑1UG1,
6SL3210‑1NE15‑8UG1,
6SL321 . ‑1NE17‑7UG1 .
6SL3210‑1NE21‑0UG1,
6SL3210‑1NE21‑3UG1,
6SL321 . ‑1NE21‑8UG1
6SL3210‑1NE22‑6UG1,
6SL3210‑1NE23‑2UG1,
6SL321 . ‑1NE23‑8UG1
6SL3210‑1NE24‑5UL0,
6SL3210‑1NE26‑0UL0
6SL3210‑ 1NE27‑5UL0,
6SL3210‑ 1NE28‑8UL0
6SL3210‑1NE31‑1UL0,
6SL3210‑1NE31‑5UL0
6SL3310-1PE33‑0AA0,
6SL3310-1PE33‑7AA0
6SL3310-1PE34-6AA0
Power
0.37 kW ... 3 kW
4 kW ... 7.5 kW
11 kW ... 18.5 kW
22 kW ... 30 kW
37 kW ... 45 kW
55 kW ... 75 kW
Power
160 kW ... 200 kW
250 kW
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Line filter according to
EN 61800‑3 Category C1
6SL3203‑0BE17‑7BA0
6SL3203‑0BE21‑8BA0
6SL3203‑0BE23‑8BA0
6SL3203‑0BE27‑5BA0
6SL3203‑0BE31‑1BA0
6SL3203‑0BE31‑8BA0
Line filter according to
EN 61800‑3 Category C2
6SL3000-0BE33-1AA0
6SL3000-0BE35-0AA0