General Purpose Input Output Module Mcb 101 - Danfoss FC 300 Design Manual

0,25 kwt - 1,2 mwt
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide

10.2 General Purpose Input Output Module MCB 101

MCB 101 is used for extension of digital and analog inputs and outputs of AutomationDrive FC 301 and AutomationDrive FC 302.
Contents: MCB 101 must be fitted into slot B in the VLT AutomationDrive.
MCB 101 option module
Extended fixture for LCP
Terminal cover
10.2.1 Galvanic Isolation in the MCB101
Digital/analog inputs are galvanically isolated from other inputs/outputs on the MCB101 and in the control card of the frequency converter. Digital/analogue
outputs in the MCB101 are galvanically isolated from other inputs/outputs on the MCB101, but not from these on the control card of the drive.
If the digital inputs 7, 8 or 9 are to be switched by use of the internal 24 V power supply (terminal 9) the connection between terminal 1 and 5 which is
illustrated in the drawing has to be established.
Illustration 10.2: Principle Diagram
MG.33.BC.02 - VLT
®
is a registered Danfoss trademark
10 Options and Accessories
10